What is the standard temperature rise for a liquid filled Transformers?

Issue:
For liquid filled MV Transformers, What is the standard heat rise?

Product Line:
Transformers

Environment:
Classes 7200, 7300, and 7400 MV transformers

Resolution:
The average temperature rise of the windings, measured by the resistance method, shall be [55°C] [65°C] when the Transformer is operated at rated kVA output in a 40°C ambient. The
Transformer shall be capable of being operated at rated load in a 30°C average, 40°C maximum ambient, as defined by ANSI C57.12.00 without loss of service life expectancy.
NOTE: The ambient temperature shall not exceed 40 degrees C, and the average ambient temperature for any 24 hour period shall not exceed 30 degrees C.


Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Help Center

Find support resources for all your needs, in one place.

  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalogue
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings