Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
What is the ratio for the MDGF ground fault module current sensor?
Product Line:
Circuit Breakers

Resolution:
The MDGF current sensor has a 1000:1 ratio.
The output signal that will appear on terminals 5 & 7 of the MDGF summing module (to the breaker terminals M2 & M3) will be 1.73 V per 1000 A of primary current.
To summarize, injecting 1 A into terminals 1-3 of the MDGF module will be equivalent to 1000 A of GF current.
1000 A of primary current will generate 1 A of secondary current input to the MDGF module. This results in 1.73 V of output on terminals 5-7.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings