What fuse does the HVMB305200 MiniBreak switch use?
Issue:
Fuses for HVMB305200 MiniBreak switch.
Product Line:
HVMB305200 MiniBreak
Environment:
Products sold in North America
Resolution:
The MiniBreak switch accepts current-limiting fuses up to 200E with a 3-inch diameter barrel. If the fuse clips do not match the installed fuses, the fuse holders can be adjusted up or down to accommodate the fuse dimensions.
The required center-to-center distance between the fuse clips is 12 inches. Since the fuse overall length is 15.89 inches and the required center-to-center dimension is 12 inches per the drawing, there should be no issue with installation.
The recommended fuses for this switch are Ferraz Shawmut Type CS-3 and Mersen fuses.