How can we help you today?

How much does the flush trim overlap the box on an NQOD panelboard with a MHC77VF cover?

Issue:
How much does the flush trim overlap the box on an NQOD panelboard with a MHC77VF cover?

Product Line:
Panelboards.

Environment:
Products sold in the United States.

Cause:
Product features.

Resolution:
The cover has .75`` overhang on each side, so has 1.5`` added to height and width.


CTA-ID : 2033979

Schneider Electric USA

Explore more

Category:

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Category:

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.