What is the power supply requirement for Micrologic trip units for Powerpact P and R frames and Masterpact breakers?
Issue:
What is the power supply requirement for Micrologic trip units for Powerpact P, R and Masterpact breakers?
Product Line:
Powerpact and Masterpact
Resolution:
The power requirement for all Micrologic trip units for Powerpact P and R frames and Masterpact breakers is 50 mA @ 24 Vdc ±5%, max ripple 1%. Use terminals F2 (+) and F1(-).

For help with Micrologic trip units and modbus communications for Masterpact and Powerpact P and R circuit breakers, consult instruction manuals:
Powerpact P, R, and Masterpact NW, NT Micrologic™ types 2.0, 3.0 and 5.0 Trip Units, see 48049-207-05
Powerpact P, R, and Masterpact NW, NT Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Trip Units, see 48049-136-05
Powerpact P, R, and Masterpact NW, NT Micrologic™ 5.0P and 6.0P Trip Units, see 48049-137-05
Powerpact P, R, and Masterpact NW, NT Micrologic™ 5.0H and 6.0H Trip Units, see 48049-330-03
What is the power supply requirement for Micrologic trip units for Powerpact P, R and Masterpact breakers?
Product Line:
Powerpact and Masterpact
Resolution:
The power requirement for all Micrologic trip units for Powerpact P and R frames and Masterpact breakers is 50 mA @ 24 Vdc ±5%, max ripple 1%. Use terminals F2 (+) and F1(-).
For help with Micrologic trip units and modbus communications for Masterpact and Powerpact P and R circuit breakers, consult instruction manuals:
Powerpact P, R, and Masterpact NW, NT Micrologic™ types 2.0, 3.0 and 5.0 Trip Units, see 48049-207-05
Powerpact P, R, and Masterpact NW, NT Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Trip Units, see 48049-136-05
Powerpact P, R, and Masterpact NW, NT Micrologic™ 5.0P and 6.0P Trip Units, see 48049-137-05
Powerpact P, R, and Masterpact NW, NT Micrologic™ 5.0H and 6.0H Trip Units, see 48049-330-03
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.