How can we help you today?

Will inductive proximity switches work on aluminum?

Issue:
Will inductive proximity switches work on aluminum?

Product Line:
Schneider Electric prox sensors sold and supported in the USA.

Environment:
Installation

Cause:
Application

Resolution:
Yes but the range is decreased using aluminum, usually achieving about 40% of the rated range using a standard target made of ASTM A36 mild steel. The one exception is aluminum foil [<0.1 mm] which makes an excellent target. This is due to an obscure principal known as the ``skin effect``. Other possibilities include the XS....KPM40 universal series which detect all metals at the same range and the XS1M18PAS20(D) which are specific for non-ferrous metals.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings