Can an EHB breaker be replaced by an EDB breaker in an NEHB panel?

Article available in these languages:

Issue:
Differences between an EDB and EHB breaker

Product Line:
NEHB Panelboards and EHB breakers

Environment:
This is for the Obsolete NEHB Panelboard and NEHB breakers

Cause:
Need a replacement for an EHB breaker in a NEHB Panelboard.

Resolution:
No, an EDB breaker cannot be used in an NEHB Panelboard. The two are not interchangeable. There is no replacement for the EHB breakers.