Can PQ fusible plug-in units be mounted on both vertical and horizontal busway?
Issue:
Can a PQ3606G be mounted vertically and horizontally?
Product Line:
Busway PQ Plug-in Units
Environment:
I-line I&II Busway
Cause:
Installation
Resolution:
It depends on the amperage of the plug-in unit.
30A, 60A, and 100A plug-in units can be mounted on either horizontal or vertical busway with no additional hardware.
200A units have two different designs. The PQ units (such as PQ3220G) are designed to be used on horizontal busway. The PS units (such as PS3220G) can only be used in vertical riser applications.
400A and 600A plug-in units can be used on a horizontal busway as standard and can be used on a vertical riser busway run when auxiliary mounting kit PBQ4060RMK is used.
For 800A, 1000A, and 1200A PTQ bolt-on units, the orientation of the busway - either horizontal or vertical - must be specified when ordering the plug-in unit.
Can a PQ3606G be mounted vertically and horizontally?
Product Line:
Busway PQ Plug-in Units
Environment:
I-line I&II Busway
Cause:
Installation
Resolution:
It depends on the amperage of the plug-in unit.
30A, 60A, and 100A plug-in units can be mounted on either horizontal or vertical busway with no additional hardware.
200A units have two different designs. The PQ units (such as PQ3220G) are designed to be used on horizontal busway. The PS units (such as PS3220G) can only be used in vertical riser applications.
400A and 600A plug-in units can be used on a horizontal busway as standard and can be used on a vertical riser busway run when auxiliary mounting kit PBQ4060RMK is used.
For 800A, 1000A, and 1200A PTQ bolt-on units, the orientation of the busway - either horizontal or vertical - must be specified when ordering the plug-in unit.
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.