How do you adjust the settings on a 9013FSG switch?

Issue:
What are the sequence in adjusting the settings on a 9013FSG switch?

Product Line:
Pressure Switches - Square D™ NEMA

Environment:
Type F—Pumptrol Water Pump Pressure Switches

Resolution:
Adjust in Proper Sequence:
1. CUT-IN Turn the large range nut down for higher cut-in pressure (clockwise) , or up for lower cut-in pressure (counterclockwise).
2. CUT-OUT Turn the smaller differential nut down for higher cut-out pressure (clockwise) which increases the differential between cut in and cut out. Up for lower cut-out pressure (counterclockwise) lowers the differential between cut in and cut out.