Coil voltage selection for LU2B12 or 32 and LUB12 or 32?
Issue:
Why does the LU2B12 or 32 need a coil voltage selection while the LUB12 or 32 does not?
Product Line:
IEC Contactors and Starters
Environment:
TeSys U Open Motor Starter
Resolution:
The reversing LU2B12/32 has a coil in the reversing module so a coil voltage must be selected. The coil voltage of the non-reversing U line is determined solely by the control module.
Why does the LU2B12 or 32 need a coil voltage selection while the LUB12 or 32 does not?
Product Line:
IEC Contactors and Starters
Environment:
TeSys U Open Motor Starter
Resolution:
The reversing LU2B12/32 has a coil in the reversing module so a coil voltage must be selected. The coil voltage of the non-reversing U line is determined solely by the control module.
Released for: Schneider Electric USA