Do TVSS units provide an indication of phase failure, and are they equipped with auxiliary contacts to support this functionality?

Issue:
Do TVSS units provide an indication of phase failure, and are they equipped with auxiliary contacts to support this functionality?

Product Line:
Surge Protective Devices (SPDs)

Environment:
Legacy I-Line™ IMA surge protective devices.

Cause:
Application question

Resolution:

Surgelogic HWA, EBA, EMA, and IMA series TVSS units are capable of detecting the loss of one or two phases. In such events, the internal monitoring circuitry will actuate a set of dry contacts (normally open or normally closed, depending on configuration). However, these units do not detect the loss of all three phases simultaneously. For complete phase-loss monitoring, including total power outage, a dedicated phase failure relay is required.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings