What auxiliary contacts can be mounted on the right side of TeSys LC1D09 to D38 contactors?

Issue:
Do we have any side-mounted auxiliary contacts that can be installed on the right side of the TeSys LC1D09 to D38 contactors?

Product Line:
Contactors and Starters - IEC

Environment:
LC1D09 - LC1D38

Resolution:
On the D09 through D38 TeSys contactors with AC coils, side-mounted auxiliary contact modules can only be installed on the left side. The right side has been designed for installation of the clip-on surge suppressor or for installation of the LAD4BB adaptor for top-mounted accessories. On the D09 through D38 TeSys contactors with DC coils side-mounted accessories cannot be used.