Are alternate mechanical lugs available for the EZM1800CB, Series M01 main breaker device?
Issue:
Product Design Features
Product Line:
Metering Equipment
Resolution:
The EZM1800CB Series M01 uses the MHP26800 main breaker and the standard lugs for this breaker accept (3) 3/0 AWG to 500 kcmil AL/CU wires per phase and (4) 3/0 AWG to 500 kcmil AL/CU wires for the main neutral.
The alternate PHASE lugs for the MH frame circuit breaker used in this device are:
(2) AL800MA7 terminals, where each terminal will accommodate two 500 - 750 kcmil AL/CU wires, or
(2) AL1000MA terminals, where each terminal will accommodate four 1/0 AWG - 350 kcmil AL/CU wires.
Alternate NEUTRAL lugs for this device include:
(1) MMLK250 kit that includes (3) 2-Barrel lugs, two of these 2-Barrel lugs can be use on this neutral in place of the standard neutral lugs. Wire range will accommodate (2) 1/0 AWG - 600 kcmil AL/CU, or (4) 1/0 AWG - 250 kcmil AL/CU.
NOTE: One extra 2-Barrel lug remains from this kit and will not be used.
For (2) 750Kcmil Max. Al/Cu wires per phase and neutral a MMSK2 lug landing kit and (2) TA8002N (manufactured by ILSCO, Purchased separately). When installing on the neutral, use the PHASE pads from this kit, which will have a small offset. DO NOT use the pad with the large offset that is marked with the letter 'N'
Product Design Features
Product Line:
Metering Equipment
Resolution:
The EZM1800CB Series M01 uses the MHP26800 main breaker and the standard lugs for this breaker accept (3) 3/0 AWG to 500 kcmil AL/CU wires per phase and (4) 3/0 AWG to 500 kcmil AL/CU wires for the main neutral.
The alternate PHASE lugs for the MH frame circuit breaker used in this device are:
(2) AL800MA7 terminals, where each terminal will accommodate two 500 - 750 kcmil AL/CU wires, or
(2) AL1000MA terminals, where each terminal will accommodate four 1/0 AWG - 350 kcmil AL/CU wires.
Alternate NEUTRAL lugs for this device include:
(1) MMLK250 kit that includes (3) 2-Barrel lugs, two of these 2-Barrel lugs can be use on this neutral in place of the standard neutral lugs. Wire range will accommodate (2) 1/0 AWG - 600 kcmil AL/CU, or (4) 1/0 AWG - 250 kcmil AL/CU.
NOTE: One extra 2-Barrel lug remains from this kit and will not be used.
For (2) 750Kcmil Max. Al/Cu wires per phase and neutral a MMSK2 lug landing kit and (2) TA8002N (manufactured by ILSCO, Purchased separately). When installing on the neutral, use the PHASE pads from this kit, which will have a small offset. DO NOT use the pad with the large offset that is marked with the letter 'N'
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.