How can we help you today?

What is the maximum size branch breaker that can be installed in an NF panelboard with a 400A main breaker?

Issue:
Branch breakers size to be installed in an NF panel with a 400A main breaker.

Product Line:
Panelboards

Environment:
NF

Cause:
Selection

Resolution:

The standard branch breakers go to 125A in 2 & 3 pole configuration.

For NF panels with a LA/LH main breaker, up to two 250a J Frame sub feed breakers can be mounted with the proper size back box and trim.
Sub-feed circuit breakers CANNOT be be field installed onto NF Panelboards with PowerPacT L main circuit breakers

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings