Can a 4 pole Micrologic breaker be used with an external NCT instead of using the 4th pole?

Issue:
Can a 4 pole Micrologic breaker be used with an external NCT instead of using the 4th pole?

Product Line:
Powerpact P, R and Masterpact

Resolution:
No, a 4 pole breaker will not read the external neutral CT input to terminals T1 and T2.