Do we have a busway offering with a 200% rated neutral?
Issue:
Busway with 200% rated neutral.
Product Line:
I-Line Busway
Environment:
Products sold in North America
Resolution:
No. The amperage of the busway will need to be double the anticipate load. ( i.e. for a 600A load, a 1200A busway will need to be ordered)
Busway with 200% rated neutral.