What is the catalog number for a sensor plug for a Powerpact P, R, or Masterpact NW, NT breaker?
Issue:
Need Sensor plug catalog number
Product Line:
Circuit Breakers
Resolution:
Note: See 2nd table for Masterpact Y frame (6p) replacement sensor plugs.
Need Sensor plug catalog number
Product Line:
Circuit Breakers
Resolution:
Note: See 2nd table for Masterpact Y frame (6p) replacement sensor plugs.
| Rating (Amps) | Part # |
|---|---|
| 100(*) | S47051 |
| 250(*) | S47052 |
| 400 | S47053 |
| 600 | S48823 |
| 630 | S33091 |
| 800 | S33092 |
| 1000 | S33093 |
| 1200 | S48824 |
| 1250 | S33094 |
| 1600 | S33095 |
| 2000 | S33982 |
| 2500 | S33983 |
| 3000 | S48825 |
| 3200 | S33984 |
| 4000 | (IEC and ANSI) S47820 |
* Cannot be installed into a circuit breaker with original sensor plug higher
than 250 A. Likewise, a circuit breaker with original sensor plug of 100 A or
250 A cannot be replaced with a sensor plug higher than 250 A.
Installation Notes:
Masterpact NT and NW: Sensor plugs are field installable down to 50% of the FRAME rating.
Example: Masterpact with a 1600 A frame can receive sensor plugs from 800-1600 A.
Powerpact P and R: Sensor plugs are field installable down to 50% of the CURRENT rating.
Example: Powerpact P frame breaker with 800 A sensor installed at the factory can only receive sensors from 400-800 A.
For complete details on installing sensor plugs and their restrictions, please see instruction bulletin 48049-145-03.
than 250 A. Likewise, a circuit breaker with original sensor plug of 100 A or
250 A cannot be replaced with a sensor plug higher than 250 A.
| Rating (Amps) | Part # |
|---|---|
| 2000 | S47821 |
| 2500 | S47822 |
| 3000 | S48826 |
| 3200 | S47823 |
| 4000 | S47824 |
| 5000 | S47825 |
| 6000 | S48827 |
| 6300 | S47826 |
Installation Notes:
Masterpact NT and NW: Sensor plugs are field installable down to 50% of the FRAME rating.
Example: Masterpact with a 1600 A frame can receive sensor plugs from 800-1600 A.
Powerpact P and R: Sensor plugs are field installable down to 50% of the CURRENT rating.
Example: Powerpact P frame breaker with 800 A sensor installed at the factory can only receive sensors from 400-800 A.
For complete details on installing sensor plugs and their restrictions, please see instruction bulletin 48049-145-03.
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.