Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
What is the main breaker kit for a 225amp NQ panel?
Issue:
What Main breaker kits are available for the 125 amp and 225amp NQ panelboards?

Product Line:
NQ Panelboards.

Environment:
Application

Cause:
Product Features

Resolution:
Following are the available Main breaker kits with Main breaker Frames listed:

NQMB2HJ Mains kit uses the 600V rated Powerpact H frame breaker 125 amp maximum for 125A interiors, or a Powerpact J frame breaker, up to 225amp maximum for 225A interiors.

NOTE: The use of 600V H and J frame breakers used as Mains in a 240V panelboard, allows accessories, i.e. Shunt trip, to be added to the Main.
The Powerpact Q Frame breakers (240V rated) have NO options/accessories that can be added or ordered for the breaker.

NQMB2Q Mains kit uses the 240V rated Powerpact Q frame breaker from 70-225A .

NQMB2KI, when using the KI frame breaker. MAIN and Breaker kit NLA, obsolete

All Main Circuit breaker kits DO NOT include the main breaker.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings