What is the Typical Required VA rating on a a control transformer for combination starter ?
Issue:
Information on the VA rating for the 8502/8536/8538/8539 NEMA Type S Starters.
Product Line:
Contactors and Starters.
Environment:
NEMA Type S Starters
Resolution:
See table below. This can also be seen on table 16.173 on page 16-58 of the Digest 177 or similar information in the current Digest. This sizing can also be used for other 8502 and 8536 based devices.
[66] Complete the contactor or starter Class and Type with the voltage code.
[67] Requires oversized enclosure. (Size 2 reversing enclosure.)
[68] Available in standard enclosure with Mag-Gard™ circuit breaker and non-fusible disconnect switch. Requires oversized enclosure with thermal-magnetic circuit breakers and fusible
disconnect switches. (Size 2 reversing enclosure.)
Information on the VA rating for the 8502/8536/8538/8539 NEMA Type S Starters.
Product Line:
Contactors and Starters.
Environment:
NEMA Type S Starters
Resolution:
See table below. This can also be seen on table 16.173 on page 16-58 of the Digest 177 or similar information in the current Digest. This sizing can also be used for other 8502 and 8536 based devices.
| NEMA Size | Starter Type | Standard Capacity (Form F4T) | Additional Capacity | ||
| 50 VA (Form F4T10) | 100 VA (Form F4T11) | 200 VA (Form F4T12) | |||
| Class 9070 Type [66] | |||||
| 0 & 1 | SB & SC | TF100 | TF150 | TF200 | TF300 [67][68] |
| 2 | SD | TF100 | TF150 | TF200 | TF300 |
| 3 | SE | TF150 | TF200 | TF300 | TF500 |
| 4 | SF | TF300 | TF300 | TF500 | TF500 |
| 5 | SG | TF100 and 8501XO20 | TF100 and 8501XO20 | TF150 and 8501XO20 | TF300 and 8501XO20 |
| 6 | SH | EO3S2 is standard | N/A | EO3FS2 and T100 | EO3S2 and TF200 |
| 7 | SJ | EO19S2 is standard | N/A | EO19S2 and TF100 | EO3S2 and TF200 |
[66] Complete the contactor or starter Class and Type with the voltage code.
[67] Requires oversized enclosure. (Size 2 reversing enclosure.)
[68] Available in standard enclosure with Mag-Gard™ circuit breaker and non-fusible disconnect switch. Requires oversized enclosure with thermal-magnetic circuit breakers and fusible
disconnect switches. (Size 2 reversing enclosure.)
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.