Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Why will the KC breakers not fit into the HCM interior?
Issue:
HCM interior cannot take KC circuit breakers

Product Line:
Panelboard, Circuit Breakers

Environment:
ILine Panelboard and Circuit Breakers

Resolution:
Size wise the KC will fit. However, the KC breaker needs a vented trim to allow the gases to escape on a high level fault. The HCM trim is not vented. But the Powerpact JJ and JL do not need the vented trim so they can be used.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings