Can the Class 8502 Type SCG__ contactor be converted to a 8536 starter by adding 9065SDO__ or 9065SS__ overload relay and 9066SC1 external reset mechanism?

Issue:
Can an overload be added to 8502 Type S contactors to convert it to one starter?

Product Line:
NEMA and Definite Purpose Contactors and Starters

Environment
NEMA Type S Contactors & Starters

Resolution:
The open style contactor inside can be modified by adding the appropriate overload relay however there are no provisions provided on the enclosure cover for mounting the 9066SC1 external reset mechanism. The solid state overload is only for three phase power systems. While you can add overload relays to the size 00, size 0, and size 1 contactors, you cannot for the size 2 and above.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Help Center

Find support resources for all your needs, in one place.

  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalogue
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings