Will a single circuit auxiliary contact block, like a LADN10 or LADN01, fit onto the Tesys D09-D38 amp contactors?

Issue:
Identifying auxiliary contact blocks for Tesys D contactors

Product Line:
IEC contactors and starters

Environment:
Tesys D Auxiliary contact blocks

Cause:
single auxiliary contact block needed for use on a Tesys D line contactor

Resolution:
No, the single pole contact block will not fit . A LADN11,LADN20, LADN02 etc will fit. Anything with 2 auxiliary contacts in one block will fit.