Can a Current Design EZM Branch Unit be added the existing Old Style EZM (Series: 1, 2 or 3) Meter Center?

Article available in these languages:

Answer

Issue:
Product Design Features

Product Line:
EZM Metering

Environment:
Main Horizontal Bus Structure

Cause:
Application

Resolution:
YES, but first keep in mind that before adding a current style EZM Branch Unit to an Existing Old Style EZM (Series: 1, 2, or 3) Meter Center, available Horizontal Wall Space and Height above Grade or Floor Level must be determined before ordering or installing. EZM Meter Centers are UL Listed as Modular Wall Mounted Panelboards. The tops and Bottoms of various EZM Cabinets may not be of the same height. EZM Cabinets are secured to the wall by use of Mounting Channels connected end to end in a Straight Line. New Style EZM Mounting Channels must be positioned 12.25" Lower on the joint wall than what was used for Old Style EZM Mounting Channels. This difference in height, along with EZM differences in Branch Unit configurations, has the potential of being an issue when dealing with acceptable Minimum and Maximum Meter Socket Heights above Grade or Floor Levels.

Old Style EZM was configured with a Horizontal Stacked (Front to Rear) Bus Structure and provided with a Sliding Joint-Pack and Single VISI-TITE Joint Bolt used for connecting Cabinets to Cabinets.
Phasing of Old Style EZM 3-Phase, 4-Wire Units:  C-Phase, B-Phase, Neutral,  A-Phase (viewed Front to Rear),
Phasing of Old Style EZM 1-Phase, 3-Wire Units:    Phase,    Neutral,    Phase  (viewed Front to Rear)

New Style EZM is configured with a Horizontal Bus Structure, placing each Bus Bar one above the other.
Left side of each New Style EZM Cabinet has Slot End Bus Bars extending 1.50" beyond the Cabinet's Side Wall.
Right side of each New Style EZM Cabinet has Bolt End Bus Bar Bars with VISI-TITE Double headed Nuts.
Phasing of New Style EZM 3-Phase, 4-Wire Units would be: A-Phase,  B-Phase,  C-Phase,  Neutral (viewed Top to Bottom)
Phasing of New Style EZM 1-Phase, 3-Wire Units would be:    Phase,  Phase,  Blank Space, Neutral (viewed Top to Bottom)

Square D offers Transition Sections for connecting New Style EZM Branch Units to Old Style EZM Meter Centers.
Four different versions are available (Drawings and Instruction Sheets are attached), each Transition Section is 10.75" Wide.
Single Phase New Style EZM Units connecting to the LEFT of an Existing Old Style EZM Meter Center requires Transition Section: EZM1TRANL
Single Phase New Style EZM Units connecting to the RIGHT of an Existing Old Style EZM Meter Center requires Transition Section: EZM1TRANR.
Three Phase New Style EZM Units connecting to the LEFT of an Existing Old Style EZM Meter Center requires Transition Section: EZM3TRANL
Three Phase New Style EZM Units connecting to the right of an Existing Old Style EZM Meter Center requires a Transition Section: EZM3TRANR.

Schneider Electric USA

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.