What type of fuses can be used in a fusible plug-in unit PQ4206G?

Issue:
Fuses that can be used in a fusible plug-in unit PQ4206G

Product Line:
I-Line Busway

Environment:
Fusible Plug-in Units

Resolution:
The PQ4206G fusible plug-in unit will accept Class H, K, or R fuses rated for 240V.

Provisions for installing Class J fuses are included in 30 through 600 A fusible devices. Conversion
to Class J fuse spacing requires relocating the load side fuse base assembly from the standard Class H fuse location to
an alternate position in the enclosure.