Can the operating handle of an enclosed circuit breaker in a M800S circuit breaker enclosure be padlocked in the ON or OFF position?
Issue:
Can the operating handle of an enclosed circuit breaker in an M800S circuit breaker enclosure be padlocked in the ON or OFF position?

Product Line:
Circuit breaker enclosure

Environment:
Padlock feature

Cause:
Feature clarification

Resolution:
The operating handle can be padlocked in the OFF position only by purchasing and field installing an S44936 Handle Padlocking Device. The S44936 is considered a ``removable`` device. The operating handle can be padlocked in the ON or OFF position by purchasing and field installing an S32631 Handle Padlocking Device. The S32631 is considered a ``fixed`` device. The external 9.25 x 9.25 cover plate must be removed to install and use the S32631.