Can the Powerpact H and J frame breakers be mounted on DIN rail?

Issue:
What is the DIN rail mounting kit for Powerpact H and J frame breakers?

Product Line:
Molded Case Circuit Breaker

Resolution:
Yes, Powerpact H & J frame 3 pole breakers can be DIN rail mounted. Use kit # S29305.
The DIN rail mounting kit requires 15 mm depth on a 35 mm DIN rail.
It fits 3 pole module breakers only. 2p HD and HG breakers will not work with it, and there is no kit for those breakers.

See instruction bulletin, 48940-239-01.