Are the P1200S, P1200R, or P1200AWK circuit breaker enclosures approved for use with a molded case switch?
Issue:
Current Product design
Product Line:
Circuit Breaker Enclosures
Resolution:
The enclosures are NOT UL listed for use with a molded case switch. The molded case switch, WITHOUT any accessories, will physically fit into the enclosure, BUT the nameplate and labeling of the enclosure ONLY identify the product as an enclosed circuit breaker.
Current Product design
Product Line:
Circuit Breaker Enclosures
Resolution:
The enclosures are NOT UL listed for use with a molded case switch. The molded case switch, WITHOUT any accessories, will physically fit into the enclosure, BUT the nameplate and labeling of the enclosure ONLY identify the product as an enclosed circuit breaker.
Released for: Schneider Electric USA