Can you put the LA4DWB on two LC1D09G7 contactors and still put a mechanical interlock between them also?
Issue:
Mount a mechanical interlock on LC1D contactors with LA4DWB
Product Line:
IEC Contactors and Starters
Environment:
Tesys D Contactors
Resolution:
Yes you can. You have to use the LAD4BB adapter on both contactors to mount the LA4DWB, but because they are mounted near the rear of the contactors, and flush to the contactors, the mechanical interlock can still be mounted also.
Mount a mechanical interlock on LC1D contactors with LA4DWB
Product Line:
IEC Contactors and Starters
Environment:
Tesys D Contactors
Resolution:
Yes you can. You have to use the LAD4BB adapter on both contactors to mount the LA4DWB, but because they are mounted near the rear of the contactors, and flush to the contactors, the mechanical interlock can still be mounted also.