Is there an alternate lug for the NQ442L4C that will take parallel 500MCM cable?
Issue:
Lug for the NQ442L4C to take parallel 500MCM cable
Product Line:
NQ Panelboard and accessories
Environment:
Products sold and used in the United States
Cause:
Replacement
Resolution:
Use the NQALM6 lugs. They will accept (2) 1/0 - 750MCM per phase.