Will an FAP circuit breaker fit into an FA enclosure?

Issue:
Product design

Product Line:
Molded Case Circuit Breaker Enclosures

Resolution:
The FAP breakers are NOT listed in the UL procedures to be used in the FA enclosures. They would physically fit, but the FA100_ series of enclosures are marked for lug-lug type circuit breakers ONLY (lugs on both the ON and OFF ends). These breakers would have an L as the third digit of the catalog number prefix (FAL, FHL, etc).