What wire size, type (solid or stranded), quantity, and torque will all the PK3GTA1 through PK27GTA ground bars accept that are used in QO and Homeline load centers?

Article available in these languages:

Issue:
Product features

Product Line:
Load Center Ground Bars

Resolution:
The terminals provided on the PK3GTA1 through PK27GTA ground bars will accept the following:
NOTES:
1)
The ground bars will accept either solid or stranded type wires.
2) As shown below the PK__GTA ground bars will accept Multiple wires for certain sizes.
3) ONLY the PK27GTA comes standard with one lug that mounts to the TOP of the ground bar and will accept (1) #6 - 2/0 Cu/Al wire

Wire Sizes for ALL the PK3GTA1 through PK27GTA ground bars:
(1) #14 - #4 CU / AL
(2 or 3) #14 CU wires
(2 or 3) # 12 CU / AL wires
(2 or 3) #10 CU / AL wires

Torque requirements:
Wire range Torque LB-IN
(1) #4 CU / AL                          35
(1) #6 CU / AL                          35
(1) #8 CU / AL                          25
(1) #10 - 14 CU, #10 - 12 AL    20
(2 or 3) #14 CU                        25
(2 or 3) #12 CU / AL                 25
(2 or 3) #10 AL                         25

SEE THE ATTACHMENT FOR THE DIMENSIONAL INFORMATION FOR THE GROUND BARS.

Schneider Electric USA

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.