What class of fuse do ALL the 60 A, 600Vac Max., heavy duty safety switches accept?
Issue:
Product design featuresProduct Line:
Heavy Duty Safety Switches
Environment:
Class of Fuses
Cause:
Application
Resolution:
HDSS = Heavy Duty Safety Switches
SCCR = Short Circuit Current Rating
ALL the 60amp, 600Vac max., HDSS accept Class H or K fuses as standard. Options include Class R fuses (field install Class R Fuse Kit) and Class J fuses (field relocate the fuse base assembly to alternate position marked in the enclosure). With Class H or K fuses installed, the switches are UL/CSA listed for use on systems with up to 10,000 RMS Symmetrical Amperes available fault current. With Class R fuses (and Class R Fuse Kit installed) or Class J fuses installed, the switches are UL/CSA listed for use on systems with up to 200,000 RMS Symmetrical Amperes available fault current.
NOTES:
1) All Square D Canadian 30 - 200amp, 600Vac, 3pole HDSS leave the factory to accept class J Fuses as standard(Including the Crouse Hinds Receptacle switches). Conversion to Class H fuses requires relocating the load side base assembly to an alternate position as marked in the enclosure.
2) DO NOT USE RENEWABLE LINK FUSES IN SQUARE D SAFETY SWITCHES. The use of renewable link fuses may adversely affect user safety, impair reliability and will void the warranty.
Released for: Schneider Electric USA
Explore more
Category:
Explore more
Category:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.