What is the current density of standard bus for HVL switchgear?
Issue:
Current density of the bus in HVL switchgear
Product Line:
HVL switchgear
Environment:
Products sold and used in the United States
Cause:
Product Features
Resolution:
600A Aluminum Bus 1/4`` x 2.5`` 960A per sq inch
600A Copper Bus 1/4`` x 2`` 1200A per sq inch
1200A Copper Bus Two - 1/4`` x 3`` 800A per sq inch
Current density of the bus in HVL switchgear
Product Line:
HVL switchgear
Environment:
Products sold and used in the United States
Cause:
Product Features
Resolution:
600A Aluminum Bus 1/4`` x 2.5`` 960A per sq inch
600A Copper Bus 1/4`` x 2`` 1200A per sq inch
1200A Copper Bus Two - 1/4`` x 3`` 800A per sq inch