Are there alternate lugs for an NQ 400 amp MLO panel that will accommodate 2 sets of 400-750 kcmil per phase?
Issue:
Optional lug for a 400 amp MLO NQ panel accepting (2) 400-750 kcmil per phase
Product Line:
NQ Panelboards
Environment:
Application
Resolution:
A 600A lug kit, catalog number NQALM6, will accomodate (2) 1/0-750 kcmil per phase and can be used in a 400A MLO panel as long as the box has enough room to met UL wire bending requirement