What is the mechanical interlock for (2) LC1F400 contactors?

Issue:
What is the mechanical interlock to build an LC1F400 as a reversing unit?

Product Line:
IEC Contactors and Starters

Environment:
Tesys F Contactors

Cause:
LC1F Contactors are not available as reversing units

Resolution:
For horizontal mounting, use an LA9FJ970 mechanical interlock and an LA9FJ976 kit of 3 power connectors. For vertical mounting, use an LA9FJ4J mechanical interlock. There are no power connectors offered with vertical mounting.