What is the difference between the J250S and JD250S circuit breaker enclosures?

Issue:
Product Features

Product Line:
Circuit Breaker Enclosure

Resolution:
The JD250S is physically smaller than the J250S and has application limitations. The JD250S is UL listed only to accept an HDL or JDL 3 pole circuit breaker. The voltage is limited to 480 Vac maximum. The SCCR is limited to 18 kAIC at 240 Vac or 480 Vac. Copper conductors must be used.