{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric USA Website

Welcome to our website.
How can we help you today?
What needs to be done when prompted PrtF Fault on ATV61 display after installing replacement MCB and/or Power Board?
Issue:
ATV61 Drive Shows PrtF Fault after replacing MCB and/or Power Board.

Product Line:
Altivar 61

Environment:
All

Cause:
Altivar 61 with PrtF Fault

Resolution:
Need to Hit Enter, select Power ID (For 18-Pulse CPD=IP00, E-Flex =IP00, MCC = IP00,M-Flex =IP00, Open or Custom Enclosed units = IP20, etc.) Set for IPxx and hold Ent key for 2 seconds.

Schneider Electric USA

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: