What Needs to Be Done When a PrtF Fault Is Displayed on an ATV61 After Installing a Replacement MCB and/or Power Board?
Resolution:
When the PrtF fault appears on the ATV61 display after installing a replacement MCB and/or Power Board, press Enter to access the menu, then select the correct Power ID.
Set the appropriate IP rating (IPxx) based on the drive configuration, for example:
- 18‑Pulse CPD: IP00
- E‑Flex: IP00
- MCC: IP00
- M‑Flex: IP00
- Open or Custom Enclosed Units: IP20
After selecting the correct IP rating, press and hold the Enter key for approximately 2 seconds to confirm the setting.
If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:
Frequently Asked Questions - Schneider Electric (se.com)
If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.