What are the ambient temperature limits in which Schneider Electric LV Transformers can be stored or operated?
Issue:
Transformers have temperature limits for storage and operation
Product Line:
LV, GPTransformers
Environment:
Applies to Ventilated and Non Ventilated Transformers by SquareD/Schneider Electric
Resolution:
Standard Schneider Electric Ventilated and TENV (Totally Enclosed Non-Ventilated) Transformers are designed for the ambient temperatures described below.
OPERATING Temperature Range:
Minimum: -40C (-40F)
Maximum: The ambient must maintain a 24 hour average of 30C (86F) with a maximum during that time of 40C (104F)
STORAGE Temperature Range:
Minimum: -60C (-76F)
Maximum: 60C (140F)
The customer must consult Schneider Electric Document 43006-850-01, attached for storage instructions.
Released for: Schneider Electric USA
Attachment(s)