Is there an additional mounting kit to mount PBQ3640G into a horizontal run?
Issue:
Mounting kit accessory to mount PBQ3640G into a horizontal run
Product Line:
I-Line Busway
Environment:
Products sold in North America
Resolution:
No. Only the vertical mounted unit requires the additional mounting kit PBQ4060RMK.
But a horizontal mounted unit should be independently supported with threaded rods to the ceiling. Contractor is responsible for the threaded rods.
Mounting kit accessory to mount PBQ3640G into a horizontal run
Product Line:
I-Line Busway
Environment:
Products sold in North America
Resolution:
No. Only the vertical mounted unit requires the additional mounting kit PBQ4060RMK.
But a horizontal mounted unit should be independently supported with threaded rods to the ceiling. Contractor is responsible for the threaded rods.
Released for: Schneider Electric USA