What is the sub feed circuit breaker kit for a for a 400 ampere NQ panel?
Issue:
What is the part number for the sub-feed breaker kit, for a 400A NQ panel?
Product Line:
Panelboards
Environment:
NQ
Resolution:
Quantity 1 of an NQSFB4Q for the Powerpact Q frame circuit breaker; or 1 of an NQSFB4HJ for the Powerpact H or J frame circuit breaker. These kits accommodate either 1 or 2 breakers.
Can also use the NQMB6PPL for PowerPacT L-frame Circuit Breakers. It requires 8.75" deep enclosures
What is the part number for the sub-feed breaker kit, for a 400A NQ panel?
Product Line:
Panelboards
Environment:
NQ
Resolution:
Quantity 1 of an NQSFB4Q for the Powerpact Q frame circuit breaker; or 1 of an NQSFB4HJ for the Powerpact H or J frame circuit breaker. These kits accommodate either 1 or 2 breakers.
Can also use the NQMB6PPL for PowerPacT L-frame Circuit Breakers. It requires 8.75" deep enclosures