Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Can PowerPacT breakers be used on a corner grounded (grounded B phase) delta system?
Issue:
Can PowerPact breakers be used on a Corner grounded (grounded B phase) delta system?

Product Line:
PowerPact Molded Case Circuit Breakers

Resolution:
Yes, the PowerPacT breakers can be used on both 3 phase 240 and 480 V corner grounded delta systems.
For 240 Vac corner grounded systems, only 2P breakers are listed.
For 480 Vac corner grounded systems, only 3P breakers are listed.
See the attached file for additional information.

Schneider Electric USA

Attachment(s)
corner gounded.xlsx [98.38 KB]
Corner-Grounded Delta 2700DB0202.pdf [124.08 KB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings