Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Can the PowerPact H and J breakers be used on a corner grounded delta system?
Issue:
Can PowerPact H and J breakers be used on a grounded B phase system?

Product Line:
Circuit Breakers

Resolution:
Yes, the PowerPact H and J breakers can be used on 3 phase, 3 wire grounded B phase systems.
  • A 2p breaker with the special 1Ø-3Ø marking may be used on a 240 Vac or 480 Vac corner grounded system (see specific breaker label for its particular interrupt rating)
  • A 3p breaker may be used on a 240 Vac or 480 Vac corner grounded system without special marking
See the attached file.

Schneider Electric USA

Attachment(s)
corner gounded.xlsx [98.38 KB]
Corner-Grounded Delta 2700DB0202.pdf [124.08 KB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings