Do any of the 400 A max CSEDs meet the EUSERC specifications and what EUSERC drawing is applicable?
Issue:
Product Design Features
Product Line:
CSED
Resolution:
1) The CU12L400CN, CU816D400CN, SU3040D400CN, SU3040D400FN, CU816D400PCN, SU2040D400PCN, and SU2040D400PFN are the ONLY 400 A CSED catalog numbers that meet the EUSERC specifications. However, not all EUSERC member utilities accept all devices that meet EUSERC standards. ALWAYS contact the local utility company for approval BEFORE obtaining and installing any device.
2) All other current 400 A catalog numbers do NOT specifically meet the EUSERC specifications. However, some EUSERC member utilities may allow them to be used.
ALWAYS contact the local utility company for approval before obtaining and installing any device.
NOTE: ALWAYS, it ismost important to obtain ALL the local utility requirements and APPROVAL BEFORE selecting and obtaining ANY metering equipment.
3) ALL the 400 A maximum rated CSED used for a single family residential meter socket would follow the EUSERC standard drawing 302 and/or 302A.
Released for: Schneider Electric USA