{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric USA Website

Welcome to our website.
How can we help you today?
Can the primaries of Control Power Transformers with fuse blocks (e.g. 9070TF100D1) be protected by non-rejection type fuses?

Issue:
Fusing of Control Power Transformers

Product Line:
LV Transformers

Environment:
Applies to Control Power Transformers by SquareD/Schneider Electric

Cause:
9070TF Control Power Transformer primaries utilize two CC type fuses

Resolution:

No. Rejection fuses must used on the primary to provide the 200,000 Ampere AIC rating.


Schneider Electric USA

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: