Can the primaries of Control Power Transformers with fuse blocks (e.g. 9070TF100D1) be protected by non-rejection type fuses?
Issue:
Fusing of Control Power Transformers
Product Line:
LV Transformers
Environment:
Applies to Control Power Transformers by SquareD/Schneider Electric
Cause:
9070TF Control Power Transformer primaries utilize two CC type fuses
Resolution:
No. Rejection fuses must used on the primary to provide the 200,000 Ampere AIC rating.