Can an NF panel Series E1 with a Factory installed 400 amp LAL36400 Main breaker, be converted to a Main lug panel?
Issue:
Can an NF panel with these characteristics be converted to a Main lug panel?
Series E1
Factory 400Amps LAL36400 Main breaker factory installed
Product Line:
NF Panelboard
Environment:
Application
Cause:
Field Changes
Resolution:
The main breaker kit should remain in place so the panel will utilize the same box and trim. The following parts will be required per panel:
(1) NFALM4 Main Lug Kit
(1) cover plate for the main breaker dead front
NOTE: THIS DOES NOT INCLUDE INTERIORS SUPPLIED W/ AN LC MAIN BREAKER.
Note: Revision 05/2017:
A cover plate for the hole in the main breaker dead front, formerly part number 80103-079-02, is obsolete and no longer available. Consider having a local metal fabricator custom-make something to replace it.
Can an NF panel with these characteristics be converted to a Main lug panel?
Series E1
Factory 400Amps LAL36400 Main breaker factory installed
Product Line:
NF Panelboard
Environment:
Application
Cause:
Field Changes
Resolution:
The main breaker kit should remain in place so the panel will utilize the same box and trim. The following parts will be required per panel:
(1) NFALM4 Main Lug Kit
(1) cover plate for the main breaker dead front
NOTE: THIS DOES NOT INCLUDE INTERIORS SUPPLIED W/ AN LC MAIN BREAKER.
Note: Revision 05/2017:
A cover plate for the hole in the main breaker dead front, formerly part number 80103-079-02, is obsolete and no longer available. Consider having a local metal fabricator custom-make something to replace it.
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.