Input Circuit Breaker Selection for SURT15K and 20KRMXLI Models
"
This document is intended to add clarity to the already available information on our website regarding input circuit breaker selection for the above models
| Power Input - Output Configuration | Input Circuit breaker for SURT15KRMXLI | Input Circuit Breaker for SURT20KRMXLI |
| Single Phase input & Single Phase output | 100A / 1 pole | 125A / 1 pole |
| Three phase input & Single phase output | 100A / 3 pole | 125A / 3 pole |
| Three phase input & Three phase output | 35A / 3 pole | 50A / 3 pole |
Note: Convenience PDU available on the unit is attached to phase L1 and limited by the input breaker size in the event of bypass
"