Will the NetBotz Fluid Detector (FD100 or NBES0301) detect 100% pure water?
Issue:
Will the NetBotz Fluid Detector (FD100 or NBES0301) detect 100% pure water
Product Line:
NetBotz
Environment:
NetBotz fluid detectors NBES0301 and NBFD0100
Cause:
Fluid detectors work using conductivity. Pure water is not conductive enough to sense.
Resolution:
The NetBotz Fluid Detector will detect distilled water but not 100% pure water.
However, the NetBotz Fluid Detector will probably work in most environments as the minute pure water makes contact with any impure surface (metal pans, floors, etc..) it will pickup ions and should immediately become conductive.
Will the NetBotz Fluid Detector (FD100 or NBES0301) detect 100% pure water
Product Line:
NetBotz
Environment:
NetBotz fluid detectors NBES0301 and NBFD0100
Cause:
Fluid detectors work using conductivity. Pure water is not conductive enough to sense.
Resolution:
The NetBotz Fluid Detector will detect distilled water but not 100% pure water.
However, the NetBotz Fluid Detector will probably work in most environments as the minute pure water makes contact with any impure surface (metal pans, floors, etc..) it will pickup ions and should immediately become conductive.
Released for: Schneider Electric USA
Explore more
Range:
Product:
Explore more
Range:
Product:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.