Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
How to Brain Dead a Back-UPS unit. (Full UPS Logic Reset)

Article available in these languages: Spanish, French

Issue:
To brain dead a Back-ups is to purge the charge in the brain of the UPS.

Product Line:
Back-UPS, Back-UPS Pro, Easy UPS

Environment:
All serial numbers.

Cause:
Troubleshooting procedure often prescribed to clear some faults or unwanted behaviors.

Resolution:
To do this, follow these steps;

  1. Disconnect any attached load.
  2. Unplug the UPS from the wall socket.
  3. Disconnect the UPS' internal battery or the battery disconnect switch if any.
  4. Push and hold the ""On"" button on the UPS for 5 seconds
  5. Reconnect internal battery or battery disconnect switch if any.
  6. Plug UPS in to known good power source.
  7. Turn UPS on.


Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings