On Powerpact H, J, or L frame breakers with interchangeable trip units, can you change the breaker rating by changing the trip unit?
Issue:
How do I know if I can replace the trip unit in my H, J, or L frame breaker?

Product line:
Molded case circuit breakers

Resolution:
Yes. The breaker needs to have either a T or R suffix after the amperage of the breaker (e.g. HJL36080T or HJL36060TU33X), which indicates they have a field replaceable trip unit.

The H frame electronic trip units are interchangeable among 60, 100, and 150 A. The H frame thermal magnetic trip units are interchangeable among 15-60 A and 70-150 A (ie. a 30 A can be changed to a 40 A, but cannot be changed to a 70 A)
The J frame electronic trip units are 250 A only. The J frame thermal magnetic trip units are interchangeable among 150-250 A.
The L frame trip units are electronic only, and are interchangeable up or down among 250, 400, and 600 A.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings