Does a shunt trip and close coil come automatically with a motor operated Powerpact P frame breaker?

Product Line:
Powerpact P frame circuit breakers

Resolution:
A shunt trip and close coil with the same voltage rating as the motor are included with a spring charging motor. An SDE contact is also included.
It is possible to order a second shunt trip or an undervoltage release device of the same or a different voltage.
Three auxiliary switches OF may also be ordered, but an SD switch is not possible on this breaker.